All brands · Refrigeration troubleshooting
Overheating / burnout, metal chips in system
What is going on
Compressor overheated or burnt out. Metal chips in the system. Almost always starved of cooling vapor, short on oil, or acid in the oil. Often it ran on after protectors tripped and were reset.
Likely causes
- No cooling vapor, from a starved system or low charge
- Lack of oil
- Contaminated oil with acid
- Running on repeated tripped-and-reset protectors without fixing the cause
Check in this order
- Measure suction superheat at the compressor
- Check oil level and sight glass
- Run an acid test on the oil
- Fit filter-driers when the system is cleaned
- Find the root cause before resetting any protector
- Recover refrigerant properly, licensed technician only
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.