Overfilled recovery cylinder, rising ambient

What is going on

A recovery cylinder that gets overfilled is dangerous, especially when the weather is warming up. As the temperature rises the liquid inside expands, and with no room left the pressure can climb fast enough to burst the cylinder or lift the relief valve. Watch the fill weight the whole time you recover, not just at the end.

Likely causes

  • Cylinder filled past its safe limit, leaving no vapor space
  • Rising ambient temperature expanding the liquid inside

Check in this order

  1. Stop recovery as soon as you approach the fill limit
  2. Transfer refrigerant to another cylinder
  3. Keep the cylinder at or below 0.8 times its water capacity times the specific gravity of the refrigerant
  4. Watch the scale during the job
  5. Store the cylinder out of the sun and away from heat

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.