All brands · Refrigeration troubleshooting
One case too cold / too warm; erratic cycling
What is going on
One case off from the rest and cycling erratically. Look at the EPR first.
Likely causes
- EPR set wrong for that case, because the setting controls case temperature
- Snap-action versus metering type mismatch, so the valve hunts
- EPR evaporator carrying more than 40% of the system load, which makes it unstable
- EEPR thermistor or controller fault, giving a wrong temperature reading
Check in this order
- Hook a gauge to the EPR access port and read the setting. Compare to what that case needs.
- Work out the load share of that evaporator against the whole system
- Read the thermistor against a thermometer on the case and against the setpoint
- Watch the valve percent open on the controller, because a valve pinned open or closed points to a sensor or control fault
- Confirm the valve type suits the application, snap-action or metering
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.