All brands · Refrigeration troubleshooting

Oil safety control trips

What is going on

What I usually find on an oil safety trip is oil that is not coming home. The control watches net oil pressure, which is pump pressure minus crankcase pressure, and trips if it stays low longer than the time delay. Oil gets lost to the system, or the pump is worn. Start with the oil return before condemning the pump.

Likely causes

  • Oil loss to the system, from no separator or a bad float
  • Oil binding in the evaporator
  • Poor oil return, from suction drier pressure drop or undersized lines
  • Worn oil pump
  • Liquid in the crankcase

Check in this order

  1. Read net oil pressure with a gauge set
  2. Check oil level in the sight glass
  3. Check the separator float
  4. Check return line solenoid and thermostat
  5. Measure suction drier pressure drop
  6. Check level regulators on rack systems
  7. Call a licensed technician before opening the oil pump

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.