Oil safety control trips
What is going on
Possible causes and checks for: oil safety control trips.
Likely causes
- Low net oil pressure (pump pressure − crankcase pressure) for longer than the delay: oil loss to system (no separator/bad float)
- Oil binding in evaporator
- Poor oil return (suction drier pressure drop
- Undersized lines)
- Worn oil pump
- Liquid in crankcase
Check in this order
- Net oil pressure, oil level, separator float, return line solenoid/thermostat, suction drier ΔP, level regulators on racks
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.