Oil drained is dark, pungent, has metal chips
What is going on
If the oil you drain from a compressor is dark, smells sharp and has metal in it, treat it as a failed or burnt compressor. Wear gloves and eye protection when you handle it, since burnout oil is acidic and can irritate skin. Do not just swap the compressor and walk away, because the acid and debris left in the lines will kill the new one.
Likely causes
- Compressor failure or burnout, with acid and metal contamination in the oil
- Mechanical wear shedding metal chips into the oil
Check in this order
- Smell and look at the drained oil, and run an acid test if you have one
- Recover the refrigerant, never vent it
- Replace the compressor
- Install burnout and suction line driers to catch what is left in the system
- Change the oil in the recovery machine afterwards so it does not carry contamination to the next job
- Find out why it failed before you start the new one
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.