Metering device orifice freezing, sludge/acid
What is going on
Metering device orifice is freezing up and you see sludge or acid. Moisture in the system.
Likely causes
- Moisture in the system, from a missing or saturated liquid-line drier
- A drier that has been heated and released its water back into the refrigerant
- Water freezes at the orifice and blocks flow, while acid and sludge form in the oil
Check in this order
- Check the liquid-line drier, it should be present and not saturated
- Replace the drier
- Evacuate the system to a deep vacuum, because water has to be boiled out
- Check for acid in the oil and clean up the system if it is present
- Recharge by weight and confirm the orifice stays clear
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.