All brands · Refrigeration troubleshooting

Low superheat, floodback, suction line sweating/frosting to compressor, compressor knock

What is going on

Possible causes and checks for: low superheat, floodback, suction line sweating/frosting to compressor, compressor knock.

Likely causes

  • Superheat set too low
  • Oversized valve (hunting)
  • Bulb picking up warm air (not insulated / bad contact → reads warm → overfeeds)
  • Valve stuck open or leaking seat
  • Pin/seat damaged by debris

Check in this order

  1. Superheat
  2. Hunting pattern over time
  3. Bulb contact/insulation
  4. External equalizer
  5. Close the valve and see if flow stops (off-cycle frost at start-up indicates leak-through)

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.