Low superheat, floodback, suction line sweating/frosting to compressor, compressor knock
What is going on
When you see low superheat, floodback, a suction line sweating or frosting all the way to the compressor and maybe a knock at the compressor, the valve is feeding too much refrigerant. Don't just keep turning the stem. Look at the bulb and the valve first, because those two cause most of it.
Likely causes
- Superheat set too low
- Oversized valve that hunts
- Bulb picking up warm air, from missing insulation or bad contact, so it reads warm and overfeeds
- Valve stuck open or leaking at the seat
- Pin or seat damaged by debris
Check in this order
- Measure superheat
- Watch the hunting pattern over time
- Check bulb contact and insulation
- Check the external equalizer
- Close the valve and see if flow stops; frost on the off cycle at start-up indicates leak-through
- Stop the unit if the compressor is knocking
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.