Low-pressure control / safety trips

What is going on

Low-pressure control tripping. Either the system is really low on suction pressure, or the control is set wrong. Check which first. Don't just reset and walk.

Likely causes

  • Low charge, restriction, leak or an evaporator freeze-up tripping the safety control
  • Control cut-out set wrong

Check in this order

  1. Set cut-out at about the saturation pressure for 10 F below the target evaporator temperature
  2. Set cut-in at about the highest allowable evaporator temperature
  3. Safety setting goes below the normal cut-out but above 0 psig
  4. Compare with table A30
  5. Check charge, filter-drier and evaporator for frost before resetting
  6. Find and fix a leak with a licensed technician if the charge is low

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.