Liquid to compressor during defrost / defrost won't terminate
What is going on
Liquid reaching the compressor in defrost, or defrost that never ends.
Likely causes
- Three-way solenoid stuck in the wrong position
- Bypass check valve around the TXV stuck, or the CPR not reducing receiver gas pressure
- Liquid line solenoid not closing, so liquid keeps feeding the hot coil
- Defrost thermostat failed, so termination never comes
- Pressure differential valve not giving the expected 20 to 40 psi drop
Check in this order
- Follow the manufacturer defrost sequence, steps 1 to 7 or 1 to 9 for your system, and confirm each valve position at each step, because defrost problems come from one valve out of order
- Check the three-way solenoid coil and plunger, since a stuck valve sends gas the wrong way
- Feel the liquid line solenoid during defrost, it should be closed and not passing
- Test the defrost thermostat for opening at its set temperature
- Measure the pressure drop across the differential valve and compare to 20 to 40 psi
- Stop the unit and call a licensed refrigeration tech if liquid is seen at the suction
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.