Liquid refrigerant reaching compressor

What is going on

Liquid reaching the compressor. Bad news, it can slug and wash out the oil. Usually vapor condensing in a long, cold suction line, or an overcharge on a cap tube system. Fix the cause before it destroys the compressor.

Likely causes

  • Vapor condensing in a long or cold suction line and running back as liquid
  • Overcharge on a cap-tube system

Check in this order

  1. Check the suction line temperature and superheat at the compressor
  2. Insulate the suction line along its length
  3. Fit an accumulator if the system calls for one
  4. Correct the charge, weigh it in to the nameplate amount
  5. Listen at start-up for knocking and recheck for frost back to the compressor

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.