All brands · Refrigeration troubleshooting
Knocking / slugging / broken valves, blown head gasket
What is going on
Possible causes and checks for: knocking / slugging / broken valves, blown head gasket.
Likely causes
- Liquid refrigerant or oil slugging — flooded start (refrigerant condensed in crankcase on off cycle)
- Leaking expansion valve on off cycle
- Overcharge, TXV superheat set too low / hunting
- Failed accumulator
- Liquid migration through oil separator
Check in this order
- Crankcase heater working
- Frost on suction line at start-up
- Superheat
- Charge
- Accumulator level
- Oil separator insulation/check valve/solenoid | 478 (452), 484 (458), 505 (479), 520 (494)
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.