Ice on lower fins, airflow blocked
What is going on
Ice building up on the lower fins and choking airflow usually means the meltwater from defrost is not leaving the coil area before it refreezes. Before anyone chips at it, shut the unit off at the disconnect and let the ice melt, since chiseling at a coil punctures tubing. Look at the whole drain path, not just the pan, and fix the reason water is staying put.
Likely causes
- Melt water refreezing before it drains: coil TD too high, drain line with poor slope, or a dead drain heater
- Drain pan heater or hot-gas loop under the pan not working
- Drain line heater failed, so the line freezes at the cold wall or box exit
Check in this order
- Power the unit off and lock it out, then let the ice melt naturally or use a gentle heat source away from the tubing
- Check the drain pan heater or hot-gas loop under the pan for heat, with a clamp meter on an electric heater
- Check the drain line heater for current and see that it is on the coldest part of the line
- Verify the drain slope with a level so water runs away without sitting in low spots
- Flush the drain with warm water once clear and watch that it leaves the box
- Run a defrost and look at the lower fins afterward to see if water still collects
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.