All brands · Refrigeration troubleshooting
Hunting / surging suction pressure and superheat swings
What is going on
Possible causes and checks for: hunting / surging suction pressure and superheat swings.
Likely causes
- Oversized valve, superheat set off MSS point, bulb location/contact poor, liquid-charged bulb on wide-range application
Check in this order
- Find MSS (A9), re-adjust ≤1/4 turn and wait 10–15 min, check valve sizing, consider cross-charged valve
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.