All brands · Refrigeration troubleshooting

High superheat, starved evaporator, low suction, partial frost on coil

What is going on

High superheat, low suction and a coil frosted only part way. Evaporator is starved. Not enough refrigerant is getting through the metering device. Don't add charge until you know why. Sort valve, bulb and restriction first.

Likely causes

  • Superheat set too high
  • Undersized valve
  • Bulb losing contact or poorly insulated bulb
  • Gas-charged head colder than bulb, so the charge condenses in the head
  • Low head pressure in cold weather
  • Plugged inlet strainer or drier
  • Evaporator pressure drop over 4 psi without an external equalizer
  • Loss of bulb charge

Check in this order

  1. Take superheat and subcooling readings. High superheat with normal subcooling points at the valve side, not low charge.
  2. Check the bulb mounting and insulation. It must be tight on a clean line section and wrapped.
  3. Warm the power head by hand. The valve should open and suction should rise. No change means a failed charge.
  4. Check head pressure. Low head in cold weather starves the valve.
  5. Check the temperature drop across the drier and inlet strainer for a restriction.
  6. Confirm the equalizer line is present and connected, since a pressure drop over 4 psi needs an external one.
  7. Compare valve capacity to the coil load.
  8. Recover refrigerant before replacing anything. Licensed technician only.

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.