High head pressure
What is going on
A high head pressure on a water-cooled unit is basically telling you the water side cannot carry away the heat. It could be scale in the tubes, not enough water, or water that is simply too warm to do the job. The good news is that you can measure all three with a couple of thermometers and a gauge, so you do not have to guess.
Likely causes
- Scaled or fouled water tubes, which act like insulation and cut heat transfer
- Low water flow, often from a water regulating valve that is stuck or set wrong
- Supply water too warm, for example from a tower or a limited supply
Check in this order
- Read the water in and out temperatures, and check the flow against what the manual or rating plate calls for
- Look at the water regulating valve and see whether it opens as head pressure rises
- If the leaving water is warm and the flow is low, suspect a restriction, plugged strainer or valve problem
- Clean the tubes with a mechanical method on shell-and-tube and rectangular tube-in-tube condensers
- Use a chemical clean on shell-and-coil condensers, following the product directions and rinsing well
- After cleaning, run the unit and compare head pressure and approach temperature to where they were before
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.