High head pressure / scaling

What is going on

High head pressure with visible scaling on an evaporative style condenser. Water distribution, airflow and water treatment are the places to look.

Likely causes

  • Spray pump or nozzles plugged, leaving dry spots on the coil because the water isn't covering it
  • Fouled coil or fill, which cuts heat transfer
  • Fan or louvers not responding to the controls, so there's not enough air
  • Water shut off in cold weather with too little air capacity to compensate
  • Drift eliminators plugged, restricting airflow

Check in this order

  1. Look at spray coverage with the pump running, every nozzle should be wetting its section
  2. Inspect coil and fill for scale and descale, because scale means higher head
  3. Check the capacity controls, fan staging and louver movement as the load changes
  4. Review the water treatment program, bleed rate and make-up, since poor treatment is what builds scale
  5. Clean the drift eliminators and the pump strainer

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.