High amps / overload at start

What is going on

If the compressor pulls high amps or trips on overload right at start, it is often fighting high suction pressure rather than being weak itself. That happens after a defrost, a long off cycle or a hot pull-down. It can also happen when the compressor tries to start against head pressure that has not equalized and the motor has low starting torque. Look at the pressures before blaming the motor.

Likely causes

  • High crankcase (suction) pressure after defrost, a long off cycle or a hot pull-down
  • No unloader on the compressor
  • Starting against unequalized head pressure with a low-torque motor

Check in this order

  1. Check suction pressure at start
  2. Check the CPR setting, which should be set to RLA
  3. Check the unloader and solenoid operation
  4. Fit a bleed-type TXV, or a hard-start kit on non-equalizing systems
  5. Measure start amps and compare with the nameplate
  6. Power off before changing any wiring

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.