High amps / overload at start
What is going on
Possible causes and checks for: high amps / overload at start.
Likely causes
- High crankcase (suction) pressure after defrost, long off cycle, hot pull-down, no unloader, starting against unequalized head pressure with low-torque motor
Check in this order
- Suction pressure at start, CPR setting (set to RLA), unloader/solenoid operation, bleed-type TXV or hard-start on non-equalizing systems
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.