Frost/sweat back on suction line; liquid to compressor
What is going on
Frost or sweat creeping back along the suction line usually means liquid is getting past the evaporator and heading for the compressor. That is not something to ignore, since liquid slugging can wreck a compressor. The valve is often too big, but charge and leaking valves cause it too.
Likely causes
- Oversized valve
- Overcharge
- Bleed-type AXV without an accumulator
- Valve leaking on the off cycle
Check in this order
- Check valve capacity against the unit
- Check the charge
- Confirm an accumulator is present
- Run an off-cycle leak test
- Watch the suction line at start-up and stop if liquid reaches the compressor
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.