All brands · Refrigeration troubleshooting

Evaporator iced up

What is going on

Evaporator is iced up on a hot-gas defrost system, so the defrost isn't happening. Check the three defrost parts in order.

Likely causes

  • Defrost solenoid stuck closed, so no hot gas reaches the coil
  • Solenoid coil open-circuit and never opening the valve
  • Bad defrost timer that never calls for defrost, because the cycle has to start somewhere

Check in this order

  1. Check the solenoid coil and the timer electrically with power off and locked out, then verify the signal when the timer calls for defrost
  2. With the timer in the closed position, rap the valve body and listen for the hot-gas surge
  3. Feel the line, it should warm up when the valve opens
  4. Replace the coil or valve if no flow, and the timer if it never energizes
  5. Manually thaw the ice and confirm a full defrost cycle afterward

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.