Evaporator excessively warm / never frosts
What is going on
If the evaporator on a hot-gas defrost system stays warm and never builds frost, the defrost bypass is probably leaking hot gas into the coil all the time. The system keeps running but the coil never gets cold enough to do its job. It's a simple thing to check once you know what to feel for.
Likely causes
- Bypass solenoid stuck open
- Solenoid coil failed open so the valve doesn't seat the way it should
Check in this order
- Feel the evaporator and the line from the solenoid to the evaporator. If both are warm, the valve is stuck open
- Open the timer circuit so the solenoid should be closed, then gently rap the valve body
- Watch the low-pressure gauge. It should drop when the valve lets go and closes
- If the pressure does not drop, replace the solenoid valve
- Check the coil electrically too, with power off and locked out
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.