Cycles on overload
What is going on
Compressor starts, trips on the overload, cools off, repeats. Start components and voltage first. Compressor last.
Likely causes
- Bad start relay
- Weak overload protector
- Low voltage at the outlet under load
- Faulty compressor
Check in this order
- Replace the relay and overload as a pair if they test bad.
- Measure outlet voltage under load. It should be 115 V within 10 percent.
- Check other loads on the circuit, and a long or thin extension cord that drops voltage.
- Try a known-good cord and ground.
- If it still trips, replace the compressor (licensed tech).
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.