All brands · Refrigeration troubleshooting
Cracked lines, leaks at fittings
What is going on
Possible causes and checks for: cracked lines, leaks at fittings.
Likely causes
- No vibration absorbers or wrong orientation, absorber twisted/stretched during install, absorber not anchored, frost under braid on cold suction
Check in this order
- Absorber orientation (horizontal, perpendicular to vibration), anchoring, insulation below 32°F
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.