Cracked lines, leaks at fittings
What is going on
Cracked lines and leaks at fittings on a refrigeration system usually come from vibration, not from the fitting itself. Absorbers are there to protect the piping, but only when they are installed right.
Likely causes
- No vibration absorbers, or absorbers in the wrong orientation
- Absorber twisted or stretched during install, which kills its job
- Absorber not anchored on the far side, so the line still whips
- Frost forming under the braid on a cold suction line, which damages the braid
Check in this order
- Check absorber orientation horizontal, perpendicular to the vibration
- Look for twist or stretch and replace the absorber if it was installed that way
- Anchor the pipe solidly just past the absorber
- Insulate the absorber area on cold lines below 32°F so frost does not form under the braid
- Leak test all joints near the compressor after repairs
- Have a licensed technician recover refrigerant before any cut or braze
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.