All brands · Refrigeration troubleshooting

Compressor won't start (general procedure)

What is going on

When a hermetic compressor will not start, work through it in a set order so you do not condemn a good compressor. Disconnect power and lock out before you touch any wiring, and discharge capacitors on units that have them. The goal is to decide whether the fault is outside the compressor or inside it. Licensed techs should handle replacement.

Likely causes

  • No power at the compressor terminals
  • Relay or overload failure
  • Motor winding fault inside the compressor
  • External circuit problem such as wiring, thermostat, relay or overload

Check in this order

  1. Confirm line voltage at the compressor terminals before anything else
  2. Check the relay and the protectors
  3. Disconnect all external wiring from the compressor
  4. Use a manual test cord with new capacitors for CSIR and CSCR types
  5. If it runs on the test cord, the fault is external: wiring, thermostat, relay or overload
  6. If it does not run on the test cord, replace the compressor

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.