All brands · Heat pump troubleshooting

Wrong superheat after line-set change; poor capacity

What is going on

After somebody changes the line set on a heat pump with a piston metering device, I look at the piston first. A wrong piston size for a long line set will throw superheat off and cost capacity. I have also found them installed backward or gummed up. Check against the manufacturer's data, since the book refers to manufacturer data for the sizes.

Likely causes

  • Wrong piston size for a long line set
  • Piston installed backward
  • Piston stuck or dirty
  • Wrong charge

Check in this order

  1. Check the piston size per the manufacturer chart
  2. Check the flow direction of the piston
  3. Clean or replace the piston
  4. Charge using the superheat method
  5. Recover refrigerant before opening, licensed technician only

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.