All brands · Heat pump troubleshooting
Won't change mode / both coils same temperature
What is going on
If a heat pump will not change modes and both coils sit at about the same temperature, the reversing valve is not shifting, or it is shifting only part way and leaking hot gas to suction. Confirm that the system is de-energized before touching the valve coil or any wiring, as the contactor and control board carry line and low voltage. Refrigerant side repairs need a licensed technician.
Likely causes
- Reversing valve solenoid coil bad, or the control signal never reaches it
- Pilot valve plugged, so the main piston never gets pushed
- Piston stuck in the mid-position, bypassing gas between ports
Check in this order
- Confirm the thermostat or board actually sends 24 V to the reversing valve coil in the mode you set
- Check the coil for voltage and, with power off, continuity
- Take line temperatures at the four ports of the valve in each mode. They should differ the way the manual shows.
- Compare the suction and discharge pressures. A weak split suggests the valve is bypassing.
- If the coil is good and the pressures are wrong, have a licensed tech replace the valve
More heat pump guides
- 2 flashes: HPS open ≥6 s; 3: discharge >263°F; 4: discharge <90°F after 1 h; 5: defrost failure; 6: discharge sensor short; 7: outdoor sensor open/short; 9: bonnet sensor fail
- Auxiliary heat indicator light is on
- Excess ice on outdoor coil
- Extremely high head pressure in heating (dual fuel)
- Insufficient heat in cold weather
- Liquid slugging / compressor damage in heating
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.