Daikin · Heat pump troubleshooting

Reversing valve will not shift

Daikin R-32 DH4S/DH5S

What is going on

Electrical and mechanical checks for a stuck reversing valve.

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. In cooling, check for 24 V at the solenoid. No voltage: check the thermostat O circuit and wiring.
  3. With voltage there, pull the coil. You should feel slight pull and hear a click. No click = stuck pilot plunger.
  4. Check the solenoid coil for continuity. Open coil: replace the coil.
  5. Try raising head pressure (block the outdoor fan discharge in cooling) and switch between cool and heat to free the slide.
  6. By temperature the discharge line should match the line after the valve, and true suction should match the suction line after the valve. A 4 degree difference means the valve is leaking. High suction pressure and a warm suction line can mean it is stuck half way.
  7. Coil good and 24 V present but the valve still will not move: replace the valve.

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting the Reversing Valve p.31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.