Daikin · Heat pump troubleshooting
Reversing valve will not shift
What is going on
Electrical and mechanical checks for a stuck reversing valve.
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- In cooling, check for 24 V at the solenoid. No voltage: check the thermostat O circuit and wiring.
- With voltage there, pull the coil. You should feel slight pull and hear a click. No click = stuck pilot plunger.
- Check the solenoid coil for continuity. Open coil: replace the coil.
- Try raising head pressure (block the outdoor fan discharge in cooling) and switch between cool and heat to free the slide.
- By temperature the discharge line should match the line after the valve, and true suction should match the suction line after the valve. A 4 degree difference means the valve is leaking. High suction pressure and a warm suction line can mean it is stuck half way.
- Coil good and 24 V present but the valve still will not move: replace the valve.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting the Reversing Valve p.31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.