Daikin · Heat pump troubleshooting

No heat: heat pump (1 stage) check order

Daikin R-32 DH4S/DH5S

What is going on

Check order when the heat pump will not heat.

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check 230 V at the unit and transformer, 24 V out, 24 V on Y and at the contactor coil.
  3. Check the contactor, compressor wiring, run capacitor, overload and windings.
  4. Make sure the thermostat is in heat. These units energize the reversing valve in cooling (O), so in heat the valve should be off.
  5. If the valve is stuck in the cool position or half way, check its wiring and solenoid, then replace the valve if needed.
  6. Check the indoor blower relay, wiring and motor.
  7. Then check the metering device and the charge.

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Heat Pump - Heating (1 Stage) p.51-52; System Operation p.12-13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.