No cooling: heat pump (1 stage) check order
What is going on
Same checks as a straight AC, plus the reversing valve.
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check 230 V at the unit and at the transformer, 24 V out of the transformer, 24 V on Y and at the contactor coil.
- Contactor, wiring to compressor, run capacitor, overload and windings, same as an AC.
- Check the thermostat is in cool and puts 24 V on O.
- Check 24 V at the reversing valve solenoid. With 24 V there, check the coil. A good coil and a valve that will not shift, or a valve stuck half way: replace the valve.
- Check the reversing valve is piped the right way.
- Check the indoor blower relay, control wiring and motor.
- Then check the metering device and the charge (subcooling / superheat).
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Heat Pump - Cooling (1 Stage) p.49-50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.