No cooling: heat pump (1 stage) check order

Daikin R-32 DH4S/DH5S

What is going on

Same checks as a straight AC, plus the reversing valve.

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check 230 V at the unit and at the transformer, 24 V out of the transformer, 24 V on Y and at the contactor coil.
  3. Contactor, wiring to compressor, run capacitor, overload and windings, same as an AC.
  4. Check the thermostat is in cool and puts 24 V on O.
  5. Check 24 V at the reversing valve solenoid. With 24 V there, check the coil. A good coil and a valve that will not shift, or a valve stuck half way: replace the valve.
  6. Check the reversing valve is piped the right way.
  7. Check the indoor blower relay, control wiring and motor.
  8. Then check the metering device and the charge (subcooling / superheat).

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Heat Pump - Cooling (1 Stage) p.49-50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.