Goodman · Heat pump troubleshooting

Reversing valve not shifting - ComfortNet heat pumps

What is going on

Heat pump stays in one mode, or suction pressure/temperature is abnormally high because the valve is stuck between positions or leaking.

Likely causes

  • No 24 V to the solenoid
  • Open solenoid coil
  • Pilot plunger stuck
  • Main slide stuck mid-position or leaking

Check in this order

  1. In cooling mode check for 24 V at the reversing valve solenoid; if none, trace the control voltage (legacy wiring: thermostat O terminal and wire).
  2. With voltage present, loosen the coil nut and slide the coil off - you should feel slight magnetic pull and hear the pilot plunger click. No click = stuck pilot.
  3. Check coil continuity; replace an open coil. Coil OK with 24 V present but valve will not move = replace the valve.
  4. To try freeing a stuck slide raise head pressure in cooling (block the outdoor fan discharge), then switch between cooling and heating.
  5. Leak test by temperature the suction line after the valve should match true suction; a difference of about 4 F or more means the valve is leaking internally.

Applies to: ComfortNet ASZC/GSZC/DSZC heat pumps

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Reversing Valve Troubleshooting p.22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.