Outdoor coil iced / no defrost - R-32 GLZS/ALZS heat pump
What is going on
Outdoor coil builds ice in heating and the unit does not go into defrost, or defrost does not end properly.
Likely causes
- Defrost thermostat not closing or mounted badly
- Defrost control board fault
- Reversing valve or outdoor fan relay problem
Check in this order
- With power on and the unit idle, jumper DFT to R (R-DFT) on the defrost board.
- Move the timer jumper to the TEST pins (use the proper jumper, not a screwdriver), call for heat - the unit should enter defrost within 21 seconds; then remove the test jumper at once.
- In defrost check 24 V across C and O; line voltage (208-230 VAC) across DF1 and DF2 (fan relay open); 24 V across W/W2 and C.
- If any reading is wrong, replace the defrost board.
- Test the defrost thermostat with a thermocouple on the adjacent tube: closing and opening temperatures depend on the part (see Specs tab).
- Power off, remove the DFT jumper and put the timer jumper back on the chosen 30/60/90 minute pins before leaving.
Applies to: R-32 GLZS4/5 and ALZS4/5 heat pumps
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), Testing Defrost Control / Defrost Thermostat p.32-33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.