Goodman · Heat pump troubleshooting
No heat - R-32 GLZS/ALZS heat pump
What is going on
Heat pump does not deliver heat in heating mode.
Likely causes
- Thermostat left in cool mode or wiring fault
- Supply or transformer problem
- Contactor, capacitor or compressor fault
- Reversing valve stuck, mis-piped or getting 24 V on O in heat
- Metering device fault
- Indoor blower fault
- Wrong charge
Check in this order
- Confirm the thermostat is in heat mode.
- Check 230 V to the unit and transformer, 24 V on Y and at the contactor coil (check pressure switches if missing).
- Contactor closed but compressor off check wiring, run capacitor, overload and windings; let a hot compressor cool before retesting.
- Compressor runs but no heat if the reversing valve is stuck between heat and cool, replace it; check for 24 V on O (it should not be energized in heat on legacy wiring).
- Check the reversing valve is piped correctly and the metering device works.
- Indoor blower off check 24 V on G, the blower relay/control wiring and the motor.
- Confirm charge with subcooling and superheat.
Applies to: R-32 GLZS4/5 and ALZS4/5 heat pumps
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), Heat Pump - Heating flowchart p.52-53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.