No mode change / wrong mode

What is going on

When a heat pump won't change modes, the reversing valve is the part everyone looks at. If the solenoid is burnt, the unit sits in its de-energized mode, which is usually heating. It's not always the valve though, so check the thermostat wiring too.

Likely causes

  • Reversing valve solenoid burnt, so the unit stays in its de-energized mode, usually heat
  • Pilot-valve capillaries plugged
  • Insufficient pressure differential
  • O versus B wiring mismatch at the thermostat

Check in this order

  1. Turn the power off, then check the solenoid coil for continuity
  2. Check the wiring is O or B as the equipment requires
  3. Meter 24 V to the solenoid when the stat calls for the mode change
  4. Listen for the valve shift
  5. A valve that won't shift needs replacing
  6. Call a licensed tech for that job

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.