Zone not conditioning — overall procedure
What is going on
Zone not conditioning. Run the whole system through its paces first. Don't chase one room until you know how the rest behave.
Likely causes
- Zone thermostat not calling or panel not responding
- Damper not opening or closing as commanded
- Bypass damper not moving with changing load
Check in this order
- Set all stats to Fan-On, or 10°F past set point
- Verify airflow at every register, with dampers open
- Turn stats off one at a time and confirm airflow stops at that zone, meaning the damper closed
- Leave one zone open while testing the last
- Watch the barometric bypass arm move as zones close, nearly open with one zone, closed with all open
- A zone that fails a step points you to its panel output, damper or wiring
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.