All brands · General troubleshooting

Crystallization / solidification

What is going on

Crystallization is what happens when the lithium bromide solution gets too concentrated for the temperature it's sitting at, and it turns to slush or solid in the lines. Think of salt dropping out of water that's gone cold. The machine can lock up completely, so you want to catch it early and work out why it happened before you restart.

Likely causes

  • LiBr concentration too high (65% will crystallize at 110°F)
  • Absorber running too cold (under 85°F)
  • Air leaking into the system and upsetting the balance

Check in this order

  1. Shut down properly and let a qualified tech check the solution before restarting
  2. Dissolve the crystals and rebalance the solution
  3. Keep air out of the system and chase down any leak
  4. Maintain the inhibitor level
  5. Run lab tests on the solution to confirm concentration
  6. Check that the absorber doesn't get pushed under 85°F

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.