Damper stuck open/closed
What is going on
A zone damper stuck open or closed is easy to sort out if you work from the panel to the damper. First figure out whether the panel is sending the right signal, then whether the damper actually follows it. Most of the time it's one of three things: wiring, a bad panel output, or a seized motor.
Likely causes
- Wiring on the wrong panel terminals
- Bad panel output
- Binding linkage, blades or debris in the damper
- Open damper motor winding
Check in this order
- At the panel, confirm the wiring is on the right terminals and the zone LED shows it is not calling
- Measure the damper terminals per the A36 table
- Disconnect the stat wires to see if the damper goes to its normal state, a wrong output means a bad panel
- At the damper, meter for voltage at the motor and trace the wire if there's none
- Cycle the lever by hand for binding linkage, blades or debris
- Ohm the motor winding, OL means the motor is bad
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.