Wide temperature swing / overshoot / lag
What is going on
The wide swings and overshoot I run into usually come from a thermostat anticipator set wrong. If it's set too high for the control current, the stat heats up slowly and the room overshoots before it shuts the call off. A large differential or a line-voltage stat will give you the same lag, so I check those before blaming the equipment.
Likely causes
- Anticipator mis-set, a rating that's too high makes the stat heat up slowly
- Differential set too large
- Line-voltage thermostat with coarse control
Check in this order
- Measure the actual control current with a meter
- Set the anticipator to the measured control current
- Look at the differential setting and tighten it if it's adjustable
- If it's a line-voltage stat, consider a low-voltage stat with a relay
- Consider an electronic thermostat for tighter control
- Watch a full cycle and confirm the swing has come in
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.