Water not heating / high head when in reclaim
What is going on
Heat reclaim not heating water, or head pressure climbing when reclaim kicks in.
Likely causes
- Three-way solenoid not diverting, so the hot gas never goes to the reclaim condenser, because of a coil or valve fault
- Reclaim condenser fouled on the water or refrigerant side, which cuts heat transfer
- Parallel reclaim condenser too small for full load, so head rises
- Check valve leaking, letting gas or liquid bypass
- Refrigerant stranded in the idle condenser, which starves the active circuit
Check in this order
- Verify the three-way valve position and coil voltage when reclaim is called
- Compare reclaim condenser capacity to the design load
- Check the check valve for leak-by, a hot line where it should be cold gives it away
- Check ORI and ORD operation, the outlet regulating valves, since stuck ones trap charge
- Measure water in and out temperatures to see whether the reclaim coil is picking up heat
- Have a licensed refrigeration tech do any refrigerant recovery or valve replacement
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.