Valve won't open/close
What is going on
A solenoid valve that won't open or close is most often just a bad coil, but I have also seen valves put in backward or with the wrong normally-open or normally-closed type, and pilot-operated ones that need a pressure difference to lift. Hear it click first, because that tells you if the coil is even trying. Turn the power off and lock it out before you touch the coil leads.
Likely causes
- Coil burned out or getting no signal
- Plunger stuck from debris or corrosion
- Wrong NC or NO type for the application
- Pilot-operated valve without enough pressure differential to open
- Valve installed backward against the flow arrow
Check in this order
- Check coil voltage with a meter while the control calls for the valve
- With power off and locked out, check coil continuity
- Listen or feel for a click when the coil energizes
- Check the pressure differential across a pilot-operated valve against what its data says it needs
- Look at the flow arrow and confirm it matches the real flow direction
- Verify the valve is the right NC or NO type for the job
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.