All brands · General troubleshooting

Ultrasonic detector alarms

What is going on

An ultrasonic leak detector that keeps alarming is hearing noise, not necessarily a leak. It listens for high-frequency sound, and fans, motors, compressors and other leaks all make plenty. If you chase every alarm you will waste a lot of time.

Likely causes

  • Noise from nearby equipment, since the detector picks up ultrasonic sound from fans, motors and other leaks
  • Background noise that masks the real leak sound
  • Sensitivity set too high for a noisy mechanical room
  • A nearby unrelated leak, such as compressed air, drowning out the one you want

Check in this order

  1. Shut off other equipment nearby that you can safely stop, because every running motor adds ultrasonic noise.
  2. Move away from fans and compressors and retest, since distance cuts the interference.
  3. Turn the sensitivity down until the alarm stops, then bring it up slowly as you approach the suspect spot.
  4. Use a shield or the rubber tip to focus the sensor on the suspect spot.
  5. Sweep joints, valves and fittings slowly and listen for the hiss pitch rise as you get close.
  6. Confirm the finding with bubble solution before you cut anything open.

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.