Smart Room Sensor not included in temperature averaging
What is going on
Sensor is left out of the averaged room temperature.
Likely causes
- Sensor reading differs from thermostat by more than 7°F
- Occupancy detection is ON and the room is not occupied
- Sensor is in direct sunlight, near discharge air, or in unconditioned space
Check in this order
- Open the sensor detail screen and read the warning message.
- Move the sensor away from sunlight, vents or unconditioned space if needed.
- Confirm the occupancy setting matches how the room is used.
- Replace the sensor if the location is suitable and readings are still wrong.
Applies to: Lennox Smart Room Sensor, not compatible with iHarmony zoning
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox S40 Smart Thermostat User Guide, p. 38-39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.