Lennox · General troubleshooting

Check Wi-Fi signal strength (RSSI) at the thermostat

S40 Smart Thermostat

What is going on

RSSI shows how strong the router signal is at the thermostat. A higher number, closer to zero, means a stronger signal. The manual gives the acceptable range as -9 to -69, which looks like a typo and should be checked against the source.

Likely causes

  • Router too far from the thermostat
  • Obstructions between router and thermostat

Check in this order

  1. Go to Menu > Settings > Wi-Fi.
  2. Select the arrow next to the Wi-Fi network name, then select it again.
  3. Read the RSSI value and the other network details on the screen: IP address, subnet mask, router IP, DNS, MAC, speed, wireless type and BSSID.
  4. If the RSSI is outside the stated range, move the router closer, add a repeater, move the thermostat, or adjust the router or extender antenna.
  5. The forget network option is on the same screen. Do not use it unless the network needs to be removed.

Applies to: Lennox S40 Smart Thermostat Wi-Fi troubleshooting

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox S40 Smart Thermostat User Guide, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.