All brands · General troubleshooting

Second stage never comes on

What is going on

Second stage not coming on during testing. Often it's the test, not the system.

Likely causes

  • Thermostat not driven far enough past set point during the test, more than 3°F is needed and it's adjustable
  • Second-stage staging differential set wider than expected
  • Terminal not actually energized when jumpering at the stat

Check in this order

  1. Check the stage differential setting at the thermostat
  2. Raise or lower the set point by more than 3°F past room temperature
  3. Force the correct terminals when testing, by the book for that stat
  4. Meter 24 V at the second-stage terminal, such as Y2 or W2
  5. If 24 V is present and the equipment still stays off, check the second-stage relay or contactor
  6. Do not jumper any safety device while testing

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.