All brands · General troubleshooting

Runs but not pumping

What is going on

Vacuum pump runs but won't pull down. Two causes: worn pump or leaking discharge valves. Two quick tests tell you which. Do them before you blame the system, because a weak pump makes a tight system look leaky.

Likely causes

  • Worn pump, low power draw and weak pulldown
  • Leaking discharge valves, so vacuum bleeds back
  • Oil contaminated or low, so the pump cannot pull deep
  • Leaking gauge or hose connection making it look like a pump problem

Check in this order

  1. Read watts or VA. Below the rating means worn.
  2. Pinch off the suction and watch the gauge. It should pull 25 to 28 in. Hg in seconds.
  3. If vacuum decays, for example 20 down to 10 in. Hg, the valves are leaking.
  4. Check the oil level and condition, and change it if it is dirty.
  5. Test with the pump isolated from hoses to rule out leaks.
  6. Replace the leaking valves or the pump.

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.