NTI · General troubleshooting
Removing the boiler from a common vent system
What is going on
Pull a boiler off a common vent and the remaining appliance is now on a vent sized for more. Spillage and CO risk. This check confirms the remaining appliance still vents properly. Do it every time a boiler comes off a common vent, and use the NFGC / ANSI Z223.1 rules.
Likely causes
- A boiler removed from a shared flue during replacement or conversion
- Remaining appliance now on an oversized vent that may not draft well
- Existing vent damaged, blocked or corroded
- Building under negative pressure from fans and dryers
Check in this order
- Seal any unused openings in the common vent.
- Inspect the vent for proper size, horizontal pitch, blockage, leakage, or corrosion.
- Close building doors and windows, close fireplace dampers, and run exhaust fans at maximum speed (not a summer exhaust fan). Run clothes dryers and other non-vented appliances.
- Run the remaining appliance continuously and test for spillage at the draft hood relief after 5 minutes with a match, candle or smoke.
- Return doors, windows, fans and dampers to normal after the test.
- Correct any improper common vent operation to meet NFGC / ANSI Z223.1.
- If you see spillage, do not leave the appliance running. Have a licensed tech resize or repair the vent.
Applies to: TRX150, TRX199, TRX199C
More general guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.