Expansion tank and air elimination
What is going on
What I usually see wrong on these jobs is air and the expansion tank. Closed-type systems depend on a correctly sized tank and a cushion of air in it, and that air has to be kept out of the piping. Bad sizing or an automatic air vent bleeding the system down gives you noisy pipes, pressure swings and relief valve discharge. These rules cover how to size and connect it.
Likely causes
- New closed-type expansion tank system being sized
- Tank tied to the wrong side of the air separator
- Automatic air vents installed that bleed off the cushion
- No micro-bubble air elimination, so air stays in the loop
Check in this order
- Size the expansion tank for total system volume, including all piping, fixtures and the boiler. Heat exchanger volume is 2.0 gal (TRX150) or 2.7 gal (TRX199/199C).
- Connect the tank to the air separator only if the separator is on the pump suction side.
- Install the system fill connection at the same point as the expansion tank connection.
- Install a micro-bubble air elimination device on every installation. Automatic air vents alone are not acceptable.
- Do not install automatic air vents on closed-type expansion tank systems. Air must stay in the system to form the air cushion.
- Check tank precharge against fill pressure before filling.
Applies to: TRX150, TRX199, TRX199C
More general guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 25, 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.