All brands · General troubleshooting
Purge runs > 2–3 minutes per cycle
What is going on
On a low-pressure chiller with a purge unit, the purge running more than 2 to 3 minutes per cycle is a warning that air is getting into the vacuum side. Noncondensables cut capacity, and moisture that gets in forms acid, so don't ignore it. Work only with the machine's procedure, and have a qualified chiller tech handle the refrigerant.
Likely causes
- Air leak into the vacuum side
- Noncondensables reducing capacity
- Moisture forming acid inside the system
Check in this order
- Log the purge run time per cycle and watch the trend
- Leak search the low-pressure side per the machine's procedure
- Repair the leak
- Purge out the noncondensables
- Recheck that purge time returns to normal
- Check oil for moisture or acid if the leak was large
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.