Oil foaming at start

What is going on

Oil foams at startup. Refrigerant has migrated into the oil sump and boils out when the compressor starts. Pressure drops, refrigerant flashes, oil turns to foam, and the bearings may be starved for a moment.

Likely causes

  • Refrigerant migration to the sump
  • Crankcase heater failed or not on long enough
  • Liquid leaking past the metering device on the off cycle
  • Compressor sitting in a cold space

Check in this order

  1. Confirm the sump heater is working and has been on long enough.
  2. Run at reduced load until the foaming clears.
  3. Check the oil level once it settles.
  4. If it repeats every start, look into why refrigerant keeps migrating.
  5. Check the metering device and solenoid for leak-through.

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.