Noisy ductwork

What is going on

Noisy ductwork usually isn't the duct's fault. What I usually find is somebody sped the blower up to cover for undersized equipment or duct, and now the air is roaring through the system. Sort out the cause of the noise first, since the fix depends on whether it is air rushing, metal panels flexing or a rumbling fan.

Likely causes

  • Velocity over 700 fpm because the blower was sped up to cover undersized equipment or duct
  • Sharp edges in the grille or duct
  • Vibrating panels, called oil-canning
  • Fan or motor rumble
  • Expansion popping as the duct heats and cools

Check in this order

  1. Remove the grille and listen to see if the noise stops
  2. Measure the velocity at the problem section
  3. Lower the velocity by reducing blower speed if the system allows, or by enlarging the duct
  4. Fit vaned or long-radius elbows
  5. Line or wrap the duct, and cross-break flat panels
  6. Add a fabric joint at the furnace and an acoustic chamber if needed

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.