All brands · General troubleshooting
No heating
What is going on
What I usually find on a zoned no-heat call is a panel or damper issue masking an ordinary furnace call. The furnace can't run if the panel never sends W, so I settle that before I touch the furnace. Once I see 24 V on W to C at the system side, the problem is in the furnace itself.
Likely causes
- Zone stats not calling or wired incorrectly
- Dampers not opening after the call
- Panel output not sending W to the furnace
- Furnace itself not responding to a good call
Check in this order
- Set all stats to heat 5°F above room and let the dampers all open after the minimum delay
- On the stat side, expect 0 V R to W, 24 V R to Y and 24 V R to C
- On the system side, expect 24 V W to C, 0 V Y to C and 24 V R to C
- No W at the system side means a panel or stat problem
- If there's 24 V W to C and no heat, move to the furnace for ignition, gas flow, safeties and pressure switches
- Gas and ignition faults are a job for a licensed tech
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.