No heat — low-voltage stat diagnostic (16 steps)

What is going on

This is a 16-step way to find out whether a no-heat call is the furnace or the thermostat and its wiring. The idea is to take the stat out of the picture at the furnace first, then work back toward the wall one measurement at a time. Do it carefully. Keep power off whenever you move a jumper, put the furnace panel back on so the door switch is properly closed, and leave anything gas related to a licensed tech.

Likely causes

  • Thermostat or subbase failed, including dead batteries on an electronic stat
  • Broken or loose thermostat wire, R or W
  • Whole thermostat cable damaged
  • Furnace control or board problem, if heat will not start at the board either
  • Mercury stat that no longer makes contact

Check in this order

  1. Turn power off, then put a jumper across R and W at the furnace board.
  2. Power on with the door switch closed, and give the furnace its normal start time. If the furnace starts, the problem is the stat or the wiring. If it does not, the problem is the furnace. Remove the jumper.
  3. At the stat subbase read R to W. You should see 25 to 27 Vac.
  4. No voltage means a wire fault, so read R to G and R to Y. If you get none, read at the source, and the R wire is bad. If you do get them, the W wire is bad.
  5. Swap to a spare conductor for the bad wire.
  6. Still nothing anywhere means the whole cable is broken and must be replaced.
  7. Voltage present, so jumper R to W at the subbase. If heat starts within the normal time, the stat is bad. Check batteries first on electronic stats.
  8. Replace mercury stats with a subbase. Remove all jumpers and confirm normal operation.

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.